AMBUS® Log Series
Medium
- Systems engineering / Software
- Thermal energy
- Water
Product Categories
- Data collection
- Landline
Processes
- Read out / Transfer
Application
- Communication devices
- Hubs
Countries
- Germany
- Switzerland
- Singapore
- Other countries
Features / Benefits
- Centralized meter reading for all meters
- Smart Metering Made Simple
- Precise Management of Meter Readings
- Meter reading via remote display—no need to enter the apartment
- On-site operation via keyboard / LCD
Technical data
- 2 versions: 20 or 60 devices
- Operating voltage (version 20) 11 VDC to 28 VDC / 13 VAC to 28 VAC; (version 60) 230 VAC (optional 110 VAC), 50/60 Hz
- Power consumption (Version 20) 5W DC / 9W AC; (Version 60) 12W
- Temperature range: 0°C to 55°C
- M-Bus voltage (Version 20) 32V (Mark, no load); (Version 60) 39V (Mark, no load)
- M-Bus quiescent current: (Version 20) max. 30 mA (20 standard loads); (Version 60) max. 90 mA (60 standard loads) Max. number
- M-Bus addresses 240
- Overcurrent threshold (Version 20) 60 mA; (Version 60) 140 mA
- Bus internal resistance (Version 20) approx. 100Ω;
(Version 60) approx. 15Ω - Transmission rate: 300 baud to 9,600 baud
- Galvanic isolation (Version 20): No; (Version 60): Yes
- Housing: Light gray plastic housing (Version 20), Protection Class IP 40, H x W x D: 58 mm x 106 mm x 96 mm
- Housing: Light gray plastic housing (Version 60), Protection Class IP 52, Dimensions: 71 mm x 165 mm x 175 mm
- Controls: 4-button membrane keypad, 2-line LCD display with 16 characters per line
- Data storage (Version 20): at least 2,000 telegrams (distributed among the number of meters); (Version 60): at least 4,000 telegrams (distributed among the number of meters) 1 MB standard, 2 MB or 4 MB upon request