AMFLO® SONIC UFA-280
Medium
- Systems engineering / Software
- Thermal energy
- Water
Processes
- Measure
Application
- Flow meter
- Building services engineering
- Local and district heating / district cooling
Countries
- Germany
- Switzerland
- Singapore
- Other countries
Features / Benefits
- Maintenance-free ultrasonic flow meter
- Wide measurement range and accurate ultrasonic measurement
- High measurement accuracy: ±0.5% of M
- Suitable for heat measurements (conformity certified) and cooling measurements (not calibratable)
- Unaffected by particles, chemical substances, or magnetite
- Easy installation and flexible mounting options
Technical data
- Nominal diameter DN 50 – DN 1200
- Nominal pressure: PN 40 bar (DN 50 – DN 250), PN 16 bar (DN 100 – DN 1200); special pressure rating PN 25/40 available upon request
- Temperature range (TFluid): Compact unit up to 120°C; separate models DN 50–DN 80, max. 150°C; DN 100 and larger, max. 200°C
- Ambient temperature (TAmb): 5°C to 55°C
- Measuring tube DN 50–DN 80 made of red brass; DN 100 and larger made of steel
- Power Supply: 230 VAC
- IP67 rating
- Measurement range: 0.01 m/s – 10 m/s
- Measurement Principle: Two-Path Ultrasound
- High measurement accuracy: ±0.5% of M
- Comes with a 5/10/20/30 m coaxial cable (please specify when ordering)
- LCD display for real-time values and status
- Approval MI004