AMTRON® SONIC D
Medium
- Thermal energy
Product Categories
- Measure
Processes
- Measure
Application
- Building services engineering
- Compact devices
- Local and district heating / district cooling
Countries
- Germany
- Switzerland
- Singapore
- Other countries
Features / Benefits
- Cost-effective meter for measuring cooling and heating
- Ultrasonic meters for energy measurement in heating and cooling systems for building services, as well as in local and district heating networks
- Static measurement principle with no moving parts; not affected by small particles
- Can also be used for cooling mode and combined heating/cooling mode with a programmable switch-over point
- Wide measurement range of 1–100 for precise energy management
- No approach or exit lanes required
- Unaffected by particles, chemical substances, or magnetite
Also available as a BIM file (IFC):
Technical data
- Nominal diameter DN 15 – DN 100
- Nominal pressure PN 16 bar / PN 25 bar
- Temperature range (TFluid): 5°C to 130°C / 150°C
- Ambient temperature (TAmb): 5°C to 50°C
- Measuring tube made of dezincification-resistant brass (DN 15 – DN 40), or cast iron or brass (DN 50 – DN 100)
- Powered by battery, 24 VAC AC power, or 230 VAC AC power
- Protection class IP54 (heat meter) IP68 (cooling meter)
- Class 2 according to EN 1434
- Installation orientation as desired (horizontal or vertical, without inlet or outlet sections)
- Also available with a wireless interface compliant with the OMS standard
- Data Logger 24 Months
- 2-wire Pt 500 temperature sensor (DN15–20 permanently attached; DN25–100 must be ordered separately)
- 2 slots for output modules (MBus, pulse input, pulse output, analog signal)
Downloads
Technical data sheets
Installation guide and user manual
EU Declaration of Conformity
Request a quote
Your inquiry regarding:
AMTRON® SONIC D