Medium

  • Thermal energy

Product Categories

  • Measure

Processes

  • Measure

Application

  • Building services engineering
  • Compact devices
  • Local and district heating / district cooling

Countries

  • Germany
  • Switzerland
  • Singapore
  • Other countries

Features / Benefits

  • Cost-effective meter for measuring cooling and heating
  • Ultrasonic meters for energy measurement in heating and cooling systems for building services, as well as in local and district heating networks
  • Static measurement principle with no moving parts; not affected by small particles
  • Can also be used for cooling mode and combined heating/cooling mode with a programmable switch-over point
  • Wide measurement range of 1–100 for precise energy management
  • No approach or exit lanes required
  • Unaffected by particles, chemical substances, or magnetite

Also available as a BIM file (IFC):

Continue to buildup.ch

Technical data

  • Nominal diameter DN 15 – DN 100
  • Nominal pressure PN 16 bar / PN 25 bar
  • Temperature range (TFluid): 5°C to 130°C / 150°C
  • Ambient temperature (TAmb): 5°C to 50°C
  • Measuring tube made of dezincification-resistant brass (DN 15 – DN 40), or cast iron or brass (DN 50 – DN 100)
  • Powered by battery, 24 VAC AC power, or 230 VAC AC power
  • Protection class IP54 (heat meter) IP68 (cooling meter)
  • Class 2 according to EN 1434
  • Installation orientation as desired (horizontal or vertical, without inlet or outlet sections)
  • Also available with a wireless interface compliant with the OMS standard
  • Data Logger 24 Months
  • 2-wire Pt 500 temperature sensor (DN15–20 permanently attached; DN25–100 must be ordered separately)
  • 2 slots for output modules (MBus, pulse input, pulse output, analog signal)